Both labels mean the building code expects your windows and doors to hold up against flying debris. The difference is in how strict it gets. The High-Velocity Hurricane Zone is a fixed area, Broward and Miami-Dade counties, with its own test protocols, a product approval for every unit and fewer exceptions. The wind-borne debris region is drawn by wind speed, takes in Palm Beach County, and allows a few shortcuts the HVHZ doesn’t.
Our office is in Deerfield Beach, on the Broward side of the line. Drive a few minutes north into Boca Raton and you’ve left the HVHZ, but you’re still in the wind-borne debris region. Here’s what that changes on a window or door job.
Where each one starts and stops
The definitions sit in Chapter 2 of the Florida Building Code. The HVHZ entry is one sentence: “This zone consists of Broward and Miami-Dade counties.”
The wind-borne debris region is defined by wind speed instead. Within the code’s hurricane-prone regions, it covers:
- Land within 1 mile of the coastal mean high water line where the design wind speed is 130 mph or more.
- Any area where the design wind speed is 140 mph or more.
Palm Beach County’s wind speed page quotes that definition and adds a line for its own permit area: “All of Unincorporated Palm Beach County is within the Wind Borne Debris Region.” The county also says interpolating between the wind speed lines isn’t allowed when deciding who is in it.
Which tests a product has to pass
In both areas, glass openings need impact rated units or an approved impact cover. Both also draw a line at 30 feet. Glass below it has to pass the large missile test, and glass above it the small missile test. What differs is the rulebook behind those tests.
- In the HVHZ, Section 1626 sends impact testing through the Testing Application Standards, TAS 201 and TAS 203, and Section 1709.5.1 requires TAS 202 for wind pressure. Operable windows and doors there also have to meet a forced entry requirement under Section 2411.3.2.1.
- Outside the HVHZ, Section 1609.1.2 accepts the national standards, ASTM E1886 and ASTM E1996, along with AAMA 506 or the TAS protocols.
Florida’s Division of Emergency Management sums up the practical result in its debris impact standards page: a product that passes the Miami-Dade standard will pass the others, but a product that passes the others “will not necessarily pass” Miami-Dade’s.
The same page points out a difference that matters for shutters. Under the Miami-Dade standard, the test missile can’t get through the shutter or break the glass behind it. The other standards let the missile poke through the shutter as long as the hole stays small enough that a 3-inch ball won’t pass.
Paperwork for every unit
Section 2410.4 of the code says that in the HVHZ, “garage doors, skylights, operative and inoperative windows shall have product approval.” Every opening on a Broward or Miami-Dade permit gets matched to an approval number. Section 2413.1 adds that any window or door without its own impact approval must be covered by “product approved storm shutters.”
How the wind load gets set
Inside the HVHZ, the code hands you the wind speed by county in Section 1620.2. For a house (Risk Category II), Miami-Dade uses 175 mph and Broward uses 170 mph. Section 1620.3 then treats every building as Exposure C, the open terrain category, unless Exposure D, the category for open water and flat unobstructed ground, applies.
Outside the HVHZ, the wind speed comes from the code’s maps, with the exact lines set locally. The exposure category is worked out for each site from the ground around it. A low house with suburban neighborhood or woods stretching at least 1,500 feet upwind can qualify for Exposure B, the category for terrain with closely spaced obstructions. The HVHZ doesn’t offer that option.
Porches and other exceptions
A few allowances exist only outside the HVHZ.
- Porches and sunrooms. Outside the HVHZ, openings in a sunroom or enclosed porch under an existing roof can go unprotected if a wall with protected openings separates that space from the house. Inside the HVHZ, the exception in Section 1626.1 covers porches enclosed with screen or removable vinyl and acrylic panels.
Replacing only some of the windows
The Florida Building Code, Existing Building has a 25 percent exception in Section 707.4 for homes that replace a few windows at a time. Within any 12 months, if the glass being replaced adds up to no more than 25 percent of the home’s total glazed area, those units don’t need impact protection. Which homes qualify is where the two areas split:
- In the wind-borne debris region, homes built under codes other than the Florida Building Code, and the replacements still have to be designed for wind pressure.
- In the HVHZ, homes built under codes in effect before September 1, 1994.
Go over the 25 percent line and the exception is gone. Miami-Dade’s fast track window permit disclosure puts it plainly: when more than 25 percent of the glazed openings are replaced, “all glazed openings replaced must meet the impact requirements.”
What it means at your house
In Broward or Miami-Dade, every window and door needs an approval good for the HVHZ, and most of the shortcuts above do not apply. In Palm Beach County, a statewide approval can work.
We check which rules cover your address before we price anything, then file the approvals with the permit. The permit and inspection steps are laid out on our process page, and you can read about the windows themselves on the impact windows page. If you’re near the county line, our Deerfield Beach and Boca Raton pages cover each side.