Florida’s code requires a vented attic to have open vent area equal to at least 1/150 of the attic’s area, or 1/300 if the vents are split between high and low on the roof. In Miami-Dade, the reroof paperwork adds that the existing ventilation can’t be reduced. In hurricane country, the bigger concern is often how those vents behave in wind-driven rain, because a vent that leaks or blows off lets water straight into the attic.
What the code requires
The Florida Building Code, Residential and the Building volume use the same basic rules:
- Each enclosed attic space needs cross ventilation, through openings protected against rain.
- The net free vent area, the open area air can actually move through, has to be at least 1/150 of the attic area.
- That can drop to 1/300 if 40 to 50 percent of the venting is high, within 3 feet of the ridge, and the rest is low, at the eaves.
- Insulation can’t block the vents, and there has to be at least a 1-inch air space between the insulation and the roof deck where the vents are.
- Openings have to keep out birds, rodents and snakes. Anything wider than 1/4 inch needs a screen or mesh.
A quick example: a house with a 2,000-square-foot attic needs about 13.3 square feet of net free vent area under the 1/150 rule, or about 6.7 square feet if the high-and-low split qualifies for 1/300.
Don’t lose ventilation on a reroof
Miami-Dade’s owner’s notification form for reroofs says it plainly: the existing amount of attic ventilation shall not be reduced. When the roof is off, vents get replaced, and that’s the time to make sure the new ones add up to at least what was there.
Our roof contracts have a line for the vent system on each job, and they include new metal vents as part of the scope. If your soffit vents are damaged, say so at the estimate.
Why vents matter in a hurricane
Fact Sheet 7.5 of FEMA’s Home Builder’s Guide to Coastal Construction deals with keeping water out of roof vents. Its main warning is that hurricane winds can drive large amounts of rain through attic vents, soaking insulation and drywall, sometimes enough to bring a ceiling down. Here’s what it says about each type:
- Soffit vents. Some water gets through almost any soffit vent, and the amount jumps when the soffit panels blow out. Vinyl and aluminum soffits set loosely in tracks are a common weak point. If the soffit moves easily when you push up on it, it probably isn’t fastened well.
- Ridge vents. These are often nailed down with ordinary roofing nails and found loose or missing after storms. A partly lifted ridge vent can act like a scoop. FEMA points to vents tested for wind-driven rain under Florida’s TAS 100(A), which usually have a baffle in front of the vent openings.
- Gable end vents. FEMA says virtually all of them will leak when the wall faces wind-driven rain. Shutters for the gable vents, installed before a storm, are the preferred fix.
- Off-ridge vents. Poorly anchored ones can flip up and funnel rain into the attic.
- Turbines. Many spin on a friction fit to the standpipe and aren’t built for hurricane winds. The head should be screwed to the pipe, and the pipe firmly fastened to the deck.
In the code’s High-Velocity Hurricane Zone, which takes in Miami-Dade and Broward, the Florida Building Code, Building requires ridge vents to carry a product approval and pass wind-driven water testing. The IBHS FORTIFIED Roof program also requires attic vents that resist wind and rain.
Ventilation, heat and your roof
FEMA notes that ventilation lowers roof covering temperatures, which usually helps the covering last, but that roof color can affect that temperature more than the amount of venting does.
What about sealing the attic?
The code also allows unvented attics, typically with air-impermeable insulation such as spray foam applied to the underside of the deck, when a list of conditions is met. FEMA calls an unvented attic a reliable way to keep wind-driven rain out, but says converting an existing house needs knowledgeable experts, because several things have to change at once. It isn’t something to decide during a reroof without a plan for the whole house.
Before your reroof
- Count your vents and note what kind they are: ridge, off-ridge, gable, soffit or turbine.
- Check the soffits by pushing up gently on a few panels.
- Ask what vents the new roof will use and how they’re fastened.
We’ll go through the attic and the vents at the estimate for a roof replacement. For the wind side of a new roof, see our hurricane roofing page. Questions? Call (786) 654-8273.